RPEQ needed - seismic restraint certification (AS 1170.4) + QLD Form 15 for 2 small inline fans, Cairns QLD We need a currently registered RPEQ (structural or mechanical) to assess an installed seismic restraint arrangement for compliance with AS 1170.4 and issue a QLD Form 15 acceptable to the building certifier (or Form 16 if the certifier requires it). Scope (pump room, social housing project, Yorkeys Knob QLD): - 2 x Fantech JetLine-250ECO inline fans (MUA-1, EAF-1), approx. 5.8 kg each - Each fan on two 40x40 HDG Walraven cantilever brackets fixed to a fire-rated concrete block wall - 4 x Friulsider X3 10x80 frame fixings (FMX3TH10080G) per fan, 50 mm embedment - Fan cradle bolted to rails through waffle-pad isolation - 300x300 rigid galv duct independently supported on cantilever brackets Provided: site photos, as-constructed drawings incl. support details, fixing datasheet, fan data. If published anchor data is insufficient, please state what pull testing you need. Deliverables: signed Form 15 + short supporting calc/letter. Turnaround: 7 days from receiving info. Please include your RPEQ number in your bid - bids without it won't be considered.